So berechnen Sie Electrical Load
learn.whatIsHeading
Electrical load calculation determines service size, feeder, and branch circuit requirements. Under-sizing risks overheating; over-sizing wastes cost.
Schritt-für-Schritt-Anleitung
- 1Sum connected loads and apply demand factors per code
- 2Typical demand factors: lighting 100%, HVAC 100%, convenience outlets 50-100%
- 3Size service for total demand + margin for future growth
Gelöste Beispiele
Eingabe
Lighting 50 kW, HVAC 150 kW, outlets 30 kW, motors 100 kW
Ergebnis
Total demand ≈ 270 kW + 25% margin = 338 kW service
Code-compliant sizing
Häufige Fehler vermeiden
- ✕Using connected load without demand factors
- ✕Neglecting motor inrush current effects
Häufig gestellte Fragen
Why use demand factors?
Not all loads run simultaneously; factors reflect realistic concurrent usage patterns.
Should future growth be included?
Yes, typically 20-25% margin allows expansion without service upgrade.