Skip to main content
Calkulon

So berechnen Sie Friction Loss

learn.whatIsHeading

Friction loss (pressure drop) in pipes and ducts represents energy loss. It's critical for pump and fan sizing.

Formel

Hazen-Williams: hf = (10.67×L×Q^1.85) / (C^1.85×D^4.87)
L
L value — Variable used in the calculation
Q
Q value — Variable used in the calculation
C
C value — Variable used in the calculation
D
D value — Variable used in the calculation

Schritt-für-Schritt-Anleitung

  1. 1Hazen-Williams: hf = (10.67×L×Q^1.85) / (C^1.85×D^4.87)
  2. 2Darcy-Weisbach: hf = f×(L/D)×(V²/2g)
  3. 3Results show required head or fan power

Gelöste Beispiele

Eingabe
PVC pipe (C=150), Q=0.05 m³/s, D=50 mm, L=100 m
Ergebnis
hf ≈ 10-12 m head loss
Significant energy requirement

Häufige Fehler vermeiden

  • Neglecting minor losses (fittings, valves)
  • Using wrong friction coefficients for pipe age

Häufig gestellte Fragen

How does diameter affect friction loss?

Loss inversely proportional to D^5 (or D^4.87); doubling diameter reduces loss 32×.

What is dynamic viscosity's role?

At low Reynolds numbers (laminar), viscosity dominates friction. At high (turbulent), roughness dominates.

Bereit zur Berechnung? Probieren Sie den kostenlosen Friction Loss-Rechner aus

Probieren Sie es selbst aus →