So berechnen Sie Motor Sizing
learn.whatIsHeading
Motor sizing matches horsepower to load requirements. Over-sizing wastes energy; under-sizing risks overheating and failure.
Formel
Calculate: P = (T × RPM) / 5252 for mechanical power
- P
- (T × RPM) / 5252 for mechanical power — (T × RPM) / 5252 for mechanical power
- T
- T value — Variable used in the calculation
- RPM
- RPM value — Variable used in the calculation
Schritt-für-Schritt-Anleitung
- 1Calculate: P = (T × RPM) / 5252 for mechanical power
- 2Apply service factor 1.15-1.25 for continuous duty
- 3Select standard motor size meeting service factor requirement
Gelöste Beispiele
Eingabe
Pump load 7.5 kW continuous, service factor 1.25
Ergebnis
Motor = 7.5 × 1.25 = 9.4 kW, select 10 kW standard motor
Next size up
Häufige Fehler vermeiden
- ✕Using continuous rating for intermittent duty
- ✕Neglecting starting current requirements
Häufig gestellte Fragen
What is service factor?
Allowable overload margin (typically 1.15-1.25); accounts for load variations and starting surges.
Why not over-size motors?
Larger motors are less efficient at partial load; match size to duty point.