Mikä on Wire Sizing?

Wire sizing selects conductor diameter to limit voltage drop and prevent overheating. Code requires ampacity matching and voltage drop limits.

Kaava

Calculate voltage drop: VD = (2×K×I×L) / (1000×A) for DC or single-phase
VD
(2×K×I×L) / (1000×A) for DC or single-phase — (2×K×I×L) / (1000×A) for DC or single-phase
K
K value — Variable used in the calculation
I
I value — Variable used in the calculation
L
L value — Variable used in the calculation
A
A value — Variable used in the calculation
DC
DC value — Variable used in the calculation

Vaiheittainen opas

  1. 1Look up ampacity from tables at operating temperature
  2. 2Calculate voltage drop: VD = (2×K×I×L) / (1000×A) for DC or single-phase
  3. 3Select wire where VD <3% feeder, <5% combined

Ratkaistut esimerkit

Syöte
I = 100 A, L = 50 m, copper wire, assume 60°C ampacity table
Tulos
AWG 6 (106 A) with ~3.1% drop, marginal
AWG 4 better choice

Yleisiä virheitä vältettäväksi

  • Using listed ampacity without derating for temperature or bundling
  • Neglecting voltage drop in long feeder runs

Usein kysytyt kysymykset

Why limit voltage drop?

Excessive drop reduces equipment performance, efficiency, and motor starting capability.

How does temperature affect wire sizing?

Higher temperature reduces ampacity; must derate if ambient >30°C.

Oletko valmis laskemaan? Kokeile ilmaista Wire Sizing-laskuria

Kokeile itse →