Formule

VD = (2 × K × I × L) / CM where K=12.9(Cu), I=amps, L=feet, CM=circular mils

Stapsgewijze handleiding

  1. 1Enter circuit amps, one-way distance, and wire gauge circular mils
  2. 2Apply the formula using your project measurements
  3. 3Add required safety factors or waste allowances per code

Uitgewerkte voorbeelden

Invoer
15A, 100 ft, 12 AWG (6530 CM)
Resultaat
VD = (2×12.9×15×100)/6530 = 5.94V = 4.95% (max 3% recommended)

Veelgemaakte fouten om te vermijden

  • Not applying code-required safety factors or derating
  • Forgetting to account for waste and cut losses in material estimates