Skip to main content
Calkulon

learn.howToCalculate

learn.whatIsHeading

Voltage Drop Calculator helps contractors and tradespeople accurately size, spec, and estimate materials and systems.

Формула

VD = (2 × K × I × L) / CM where K=12.9(Cu), I=amps, L=feet, CM=circular mils

Пошаговое руководство

  1. 1Enter circuit amps, one-way distance, and wire gauge circular mils
  2. 2Apply the formula using your project measurements
  3. 3Add required safety factors or waste allowances per code

Решённые примеры

Ввод
15A, 100 ft, 12 AWG (6530 CM)
Результат
VD = (2×12.9×15×100)/6530 = 5.94V = 4.95% (max 3% recommended)

Распространённые ошибки

  • Not applying code-required safety factors or derating
  • Forgetting to account for waste and cut losses in material estimates

Готовы посчитать? Попробуйте бесплатный калькулятор Voltage Drop

Попробуйте сами →

Настройки