Skip to main content
Calkulon

learn.howToCalculate

learn.whatIsHeading

Voltage Drop Calculator helps contractors and tradespeople accurately size, spec, and estimate materials and systems.

Formel

VD = (2 × K × I × L) / CM where K=12.9(Cu), I=amps, L=feet, CM=circular mils

Steg-för-steg-guide

  1. 1Enter circuit amps, one-way distance, and wire gauge circular mils
  2. 2Apply the formula using your project measurements
  3. 3Add required safety factors or waste allowances per code

Lösta exempel

Ingång
15A, 100 ft, 12 AWG (6530 CM)
Resultat
VD = (2×12.9×15×100)/6530 = 5.94V = 4.95% (max 3% recommended)

Vanliga misstag att undvika

  • Not applying code-required safety factors or derating
  • Forgetting to account for waste and cut losses in material estimates

Redo att beräkna? Prova den kostnadsfria Voltage Drop-kalkylatorn

Prova själv →